Tracer Wire Copper Conductor

The Tracer Wire Copper Conductor is suitable for installation in ambient temperatures of -40° C (-40° F).

This wire is available in solid or stranded conductor construction, in a variety of diameters, and is usually shipped on 300 m reels. Customer colour many insulation are available.

Three (3) different insulation types are available from ICCC:

Type RW 90:

  • Designed for circuits not exceeding 600 volts;
  • Manufactured in accordance with CSA C22.2, No. 75;
  • Maximum conductor temperature of 90° C (195° F) in wet or dry environments;
  • XLP insulation.

Type RWU:
  • Designed for circuits not exceeding 1000 volts;
  • Manufactured in accordance with CSA C22.2, No. 38;
  • Maximum conductor temperature of 90° C (195° F) in wet or dry environments;
  • XLP insulation.

Type TWU:
  • Designed for circuits not exceeding 600 volts;
  • Manufactured in accordance with CSA C22.2, No. 75;
  • Maximum conductor temperature of 60° C (140° F) in wet or dry environments;
  • Thermoplastic insulation;
  • Approved for direct burial installation.